Application / Properties

The distributions are used for safeguarding,
controlling, switching and distributing electric
power, e�g� main, lighting, heating, control and
intrinsically safe circuits, etc� (see Technical
Data for temperature classes, explosion groups,
permissible ambient temperatures)�
For controlling electric machines and installa-
tions in potentially explosive atmospheres, the
enclosures can be fitted with control and
indicating components that have been certified
for this purpose within the scope of the
approvals�
Specially marked control unit components can
be operated in "intrinsically safe circuits" �
The electric limiting values applicable to
"intrinsic safety" shall be observed.
The function of circuit breakers and ELCBs
(RCDs) with circuit breakers shall be checked
after several short circuits�
An ELCB (RCD) does not prevent the sensation
caused by an electric shock, but it limits the
duration of the current flow through the human
body to such a short time that the probability of
a fatal effect is reduced to a negligible amount�
FI or FI/LS with the symbol K on the
type lable have a short time delay of
10 ms�
Once the cause for the tripping of the ELCB
(RCD) has been eliminated, it is reset by
switching the toggle to the "ON" position�
64
Explosion-protected distributions GHG 619; EXKO
By cutting out the switch collar in the respec-
tive locking position, the small control switches
can be locked with a padlocking facility� (Ø lock
shackle 5mm)�
The front actuators of the Ex 23 control
switches feature a drilled hole, Ø 5�5mm, in the
respective locking position on the switch collar
and can, therefore, be locked with a padlocking
facility of the type mentioned above�
When required, the Ex 28 and Ex 29 control
switches are provided with a locking facility that
also allows them to be locked with a padlock�
Details of the electric contacts are given on the
Wall fixing
base of the component�
lugs
The version with gold-tipped contacts is marked
with a "G" or with colour (see Technical Data,
for max� current load)�
To ensure reliable isolation, the normally closed
contacts are designed as forced break contacts
(optional Ex 28/Ex 29 with forced make
contacts)�
Where required, the bases are fitted with 0�6 W
resistors, fine-wire fuses and diodes (max� pow-
er dissipation 1 W)�
The measuring instruments AM 72 and AM 45
are used for the local indication of electrical
values� (See Technical Data, for the type of
movement, accuracy and connections)�
With measuring instruments for c�t� connection
n/1A (fig� 4, item 2), the interchangeable scales
(fig� 4, page 28) can be exchanged via a flap on
the upper part of the measuring instrument�
Observe the rated diversity factors accordance
to IEC/EN 60439 4�7 when equip the
distributions�
Information on the safe use of third-party
products, unless non specified in these
operating instructions, have to be requested
from the respective manufacturer of the
equipment.
The data according to sections 3 and 4 shall
be taken into account during use.
Applications other than those described are
not permissible without a written declara-
tion of consent from the manufacturer.
During operation the instructions stated in
section 7 of the operating instructions shall
be observed. These operating instructions
also apply as instructions for the replace-
ment or addition to individual flameproof
components.
The sole responsibility with respect to the
suitability and proper use of these boxes lies
with the operator.
5.1
Application / Properties
Flange sockets
The flange sockets are used for the power
supply of local controls with varying locations,
as well as of electrical installations, mobile
machinery and driving gear in hazardous areas�
The low-voltage plugs and sockets are fitted
with a load switch and can be used up to max�
16 A / 32 A (see technical data)� The plugs and
sockets can generally be used for the voltage
range laid down in IEC/EN 60309 (e�g� UN 400V
that corresponds to the voltage range 380-415V)�
The apparatus connected to the plug shall
be suitable for the applied mains voltage.
In order to switch on the socket, the plug is
inserted, pushed fully home and then turned
through approx� 45° to the right� Thereby the
plug is locked in the socket�
For switching off and pulling the plug, proceed
in inverse Order�
After a short in the circuit, the functioning of
the plug and socket system and of the plugs
has to be checked.