Contact arrangement
Dimension drawings
Dimensions in mm
X = Fixing dimensions
Main current switch
Dimensions 40 A
80 A
A
34
38,5
B
87
130
C
73
131
D
118
165
X
115
141
F
128
161
G
6,3
9,5
The technical data relates to standard built-in apparatus�
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed�
50
Explosion-protected distributions GHG 619; EXKO
1.15

Thermal overcurrent relay

EC type examination Certificate:
Explosion protection:
IECEx type examination certificate:
Temperature range:
Rated voltage:
Control voltage:
Continuous operation current I
Tripping current:
Function:
Terminal cross section:
Switch contacts 1�2�3�4�5�6
Control contacts 95� 96� 97 � 98
Component size:
Weight:
1.16

Main current switch, 4-pole, 40 A, 80 A, 125 A and 180 A

EU type examination Certificate:
Switch 40 A
Switch 80 A
Switch 125 A und 180 A
Explosion protection:
Temperature range:
Rated voltage:
Switch
Rated current:
Back-up fuse, max�
Switching capacity AC 3
Switching capacity AC 3
Switching capacity AC 3
Switching capacity AC 3
(IEC/EN 60947-5-1)
Weight ca�:
Terminal cross section:
Switch 40 A
Switch 80 A
Switch 125 A
Switch 180 A
Aux� contacts
Minimum terminal cross section/ Terminal for T6:
125 / 180 A
Switch 40 A
Switch 80 A
16
Switch 125 A
159
Switch 180 A
146
194
170
193
12
PTB 98 ATEX 1087U
Ex de II C
IECEx BKI 07 �0038U
for use in temperature classes T4 - T6
up to 690 V AC
up to 275 V* AC
(*Further control voltages on request)
:
6 A
th
0�16 A �������� 16 A
thermal release with phase-failure protection
max� 2x 10 mm²
max� 2x 2�5 mm²
2
approx� 1�10 kg
BVS 14 ATEX E 085 U
BVS 12 ATEX E 127 U
BVS 21 ATEX E 079 U
Ex db eb IIC Gb
for use in temperature classes T4 - T6
up to 690 V AC
40 A
40 A
80 A
230 V:
40 A
400 V:
40 A
500 V:
40 A
690 V:
32 A
1�20 kg
2�5 Nm
2x 4 - 16 mm²
3�5 Nm
2x 4 - 25 mm²
6�0 Nm
2x 4 - 70 mm²
6�0 Nm
1x 50 - 120 mm² (with cable lug 1x 120mm²)
2�5 Nm
2x 1�5 - 4�0 mm²
1x 10 mm²
1x 16 mm²
1x 50 mm²
1x 120 mm²
GB
3�0 Nm
1�5 Nm
80 A
125 A
180 A
80 A
125 A
180 A
160 A
200 A
250 A
80 A
125 A
180 A
80 A
125 A
180 A
80 A
125 A
150 A
63 A
125 A
125 A
3�68 kg
6�30 kg
6�50 kg
(with cable lug 1x 35mm²)