Front element of signal lamp
Explosion-protected distributions GHG 619; EXKO

1.19 Double cable end box

EPL:
Cable cross section:
Test torques Cable clamp for strain relief
Operating temperature:
Degree of protection to EN/IEC 60529:
(Not suitable for zone 2D and 3D acc� to EN 60079-10-2)
1.20

Signal lamp GHG417 1805 R....

EU-Type Examination Certificate:
Marking acc� to 2014/34/EU
and standard of series EN 60079:
IECEx type examination certificate:
Category of application to
standard of series IEC 60079:
Permissible operating temperature range:
Max� service temperature
(Other temperatures possible with special versions)
Perm�ambient temperature in original packing:
Degree of protection to EN/IEC 60529:
Rated voltage /Rated current:
"e" increased safety (Ex db eb)
"e" increased safety (Ex db eb)
"i" intrinsically safe version (Ex db ia) 10 V
Ex-i Datas:
U i
I i
Ci
Li
Pi
Supply terminal:
Test torques:
Weight:
Gb
Ø 21 mm ��� Ø 45 mm
Ø 46 mm ��� Ø 72 mm
15 Nm
-20 °C ��� +80 °C
IP54
IBExU 12ATEX 1047 U
II 2 G Ex db eb IIC Gb
II 2 G Ex db ia IIC Gb
IECEx IBE 13�0031U
Ex db eb IIC Gb
Ex db ia IIC Gb
-55 °C ��� +80 °C
+80 °C
-55 °C ��� +80 °C
(installed condition)
IP 66
20 V
��� 254 V AC/DC
12 V
��� 24 V
AC/DC
��� 30 V
DC
30 V
120 mA
0
0
750 mW
1x / 2 x 0�5 - 2�5 mm²; 1 x 4�0 mm² single wire
2�5 Nm
approx� 0�15 kg
GB
4 ��� 15 mA
max� 24 mA
max� 38�7 mA
53

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Crouse-hinds ghg 619Crouse-hinds exko

Inhaltsverzeichnis