Fig� 1�4�
Connection Main contact
Fig� 1�4 a
Connection Main contact
1-pole + N
Aux� contact
Signal contact
The technical data relates to standard built-in apparatus�
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed�
Explosion-protected distributions GHG 619; EXKO
1.4

ELCB (RCD), 2- and 4-pole GHG61

EC-Type Examination Certificate:
Explosion protection:
IECEx type examination certificate:
Temperature range:
Rated voltage:
Rated current:
Short-circuit protection:
Back-up fuse:
Tripping current:
Terminal cross section:
Test torques:
Component size:
Weight
* ELCB with circuit breakers and signal contacts are built into component enclosures in the next size�
1.4 a
Circuit breaker, 1-pole+N, with ELCB (RCD) GHG61
EC-Type Examination Certificate:
Explosion protection:
2-pole
IECEx type examination certificate:
Temperature range:
Rated voltage:
Rated current:
Short-circuit protection:
Back-up fuse:
Tripping current ELCB:
Terminal cross section:
Test torques:
Component size:
Weight:
Contact arrangement:
* ELCB with circuit breakers and signal contacts are built into component enclosures in the next size�
PTB 98 ATEX 1087U
Ex de II C
IECEx BKI 07 �0038U
for use in temperature classes T4-T6
Main contact
up to 440 V AC
Main contact
up to 63 A
10 kA
max� 100 A gG
30 mA (300 mA on request)
Main contact
max� 2x 10 mm²
3,0 Nm
2
approx� 0,94 kg
2-pole *
PTB 98 ATEX 1087U
Ex de II C
IECEx BKI 07 �0038U
for use in temperature classes T4-T6
Main contact
up to 440 V AC
ELCB
up to 63 A
Circuit breaker
from 1,0 A up to 32 A (40 A)
Aux� contact
max� 5 A
10 kA
ELCB
max� 100 A gG
Circuit breaker
dep� on rated current up to 100A
30 mA (300 mA on request)
Main contact
max� 2x 10 mm²
3,0 Nm
2*
approx� 0,95 kg
1-pole + N
GB
Aux� contact
up to 250 V AC
Aux� contact
max� 5 A
Aux�contact
max� 2x 2,5 mm²
1,5 Nm
4
approx� 1,56 kg
4-pole
Aux� contact
up to 250 V AC
Aux�/Signal contact
max� 2x 2,5 mm²
1,5 Nm
3*
approx� 1,27 kg
2-pole