Herunterladen Inhalt Inhalt Diese Seite drucken

1�2 Technical Data System 250 A; 1.2.1 Technical Data System 315 A - Eaton CROUSE-HINDS Serie Betriebsanleitung

Vorschau ausblenden Andere Handbücher für CROUSE-HINDS Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Explosion-protected distributions GHG 619; EXKO
1.2
Technical data system 250 A
Bus bar rail system:
EC type examination certificate:
Explosion category and marking acc� to
EN 60079-0
IECEx certificate:
Category of application:
IEC 60079-0
Rated voltage:
Rated current:
Rated short time current:
Rated short circuit current:
Rated cross-section of the bus bar:
Cross-sectional:
Support spacing for Is to 35 kA
* In reducing the peak short-circuit current, the support intervals can be increased after consultation with CCH and with appropriate
documentation�
Overall length of unit:
Permissible ambient temperature:
Temperature range:
Perm�ambient temperature in original packing:
original packaging, in a darkened, enclosed and dry room
Test torques:
Fixing screws bus bar system:

1.2.1 Technical data system 315 A

Bus bar rail system:
EC type examination certificate:
Explosion category and marking acc� to
EN 60079-0
IECEx certificate:
Category of application:
IEC 60079-0
Rated voltage:
Rated current:
Rated short time current:
Rated short circuit current:
Rated cross-section of the bus bar:
Cross-sectional:
Support spacing for Is up to 47 kA
* In reducing the peak short-circuit current, the support intervals can be increased after consultation with CCH and with appropriate
documentation�
Overall length of unit:
Permissible ambient temperature:
Temperature range:
Perm�ambient temperature in original packing:
original packaging, in a darkened, enclosed and dry room
Test torques:
Fixing screws bus bar system
1x 12 mm x 5 mm
BVS 11 ATEX E 068 U
2014/34/EU
and standard:
II 2 G Ex e IIC Gb
IECEx BVS 11�0048U
Ex e IIC Gb
690 V
250 A
4 kA
35 kA
60 mm²
1�5 mm² up to 185 mm²
300 mm*
6300 mm
-55 °C up to +55 °C
-55 °C up to +100 °C
-20 °C up to +40 °C
2,5 Nm
2x 12 mm x 5 mm
BVS 11 ATEX E 068 U
2014/34/EU) and standard
:
II 2 G Ex e IIC Gb
IECEx BVS 11�0048U
Ex e IIC Gb
690 V
315 A
9 kA
47 kA
120 mm²
1�5 mm² up to 185 mm²
300 mm*
6300 mm
-55 °C up to +55 °C
-55 °C up to +100 °C
-20 °C up to +40 °C
2�5 Nm
GB
37

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Crouse-hinds ghg 619Crouse-hinds exko

Inhaltsverzeichnis