Herunterladen Inhalt Inhalt Diese Seite drucken

1.28 Flange Socket 16 A - Eaton CROUSE-HINDS Serie Betriebsanleitung

Vorschau ausblenden Andere Handbücher für CROUSE-HINDS Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1.28 Flange socket 16 A

Flange socket
the series of standards EN 60079:
Marking acc� to 2014/34/EU and
Flange socket GHG 511 8
Category of application and the series of standards IEC 60079:
Rated voltage:
GHG 511 -
GHG 511 -
GHG 511 -
(Special voltages and various contact-marking are possible on request�)
Type
Flange socket GHG 51�8���R���� / 3p (default temperature range)
��
Flange socket GHG 51�8���R�1�� / 3/4/5p (Extendet temperature range)
Flange socket GHG 51�8���R���� / 4/5p (default temperature range)
(Special versions permit deviating temperatures)
Back-up fuse:
without thermal protection
with thermal protection
Switching capacity AC 3
Switching capacity AC 3
Switching capacity AC 3
Protection category acc� to EN/IEC 60529
(1)
with closed and secured hinged cover as well as combinations properly plugged together�
Attention! When the Plugs GHG 543/531 is insert with sockets of the series GHG 511,
the "IP" protection category of the combination is reduced to the minimum protection category "IP 54"�
Insulation class acc� to IEC/EN 61140:
Cable entry:
Suitable cables
Flange socket
Test torques:
Supply terminals
Dimensions in mm
X = fixing dimensions
Flange socket
2-pol� + PE
60
Explosion-protected distributions GHG 619; EXKO
ATEX type examination certificate
GHG 511 8�
BVS 15 ATEX E 101 U
D II 2 G Ex db eb IIC / IIB / IIB+H2 Gb
D II 2 D Ex tb IIIC / IIIB Db
Ex db eb [ia] IIC / IIB / IIB+H2 T6 / T5 Gb
Ex tb IIIC T80 °C Db
3-pole
up to 415 V, 50/60 Hz; max 400 Hz
4-pole
up to 690 V, 50/60 Hz; max 400 Hz
5-pole
up to 690 V, 50/60 Hz; max 400 Hz
Gasgroupe
IIB
IIB+H
IIC
2
maximum rated current
16 A
-
-
-
16 A
-
-
-
16 A
16 A
16 A
-
10 A
10 A
-
-
-
16 A
-
-
10 A
16 A
16 A
-
-
-
16 A
GHG 511
20 A
35 A gG
3-pole:
250 V/16 A
4-pole:
400 V/16 A
5-pole:
500 V/16 A
IP 66 (catalogue version)
I – with metal flange or metal cable entries
II - is complied with by devices
(catalogue version)
Flange socket
2�5 Nm
Flange socket
4/5-pol�/ + PE
Perm� ambient temperature:
-45 °C ��� +55 °C
-30 °C ��� +55 °C
-20 °C ��� +55 °C
-55 °C ��� +45 °C
-55 °C ��� +55 °C
-20 °C ��� +45 °C
-20 °C ��� +55 °C
-55 °C ��� +55 °C
-20 °C ��� +55 °C
(1)
Supply terminals /
Clamping range:
2 x 1�5 - 4�0 mm
2
2 pol� + PE
GB
IECEx Certificate of
Conformity:
IECEx BVS 15�0088 U
Install protected against
X
ATEX - IEC
higher mechanical risk� Max 4J
Stripped wire length
10 mm
Code Zone 1
3 pol� + PE 3 pôl� + N + PE