18. Technical data

Supply voltage
1 x 230 V ± 10 %, 50/60 Hz, PE.
Motor protection
The pump requires no external motor protection.
Enclosure class
IPX4D (EN 60529).
Insulation class
F.
Relative air humidity
Maximum 95 %.
Ambient temperature
0 °C to +40 °C.
During transport: -40 °C to +70 °C.
Temperature class
TF110 (EN 60335-2-51).
Liquid temperature
Continuously: -10 °C to +110 °C.
Stainless-steel pumps in domestic hot-water systems:
In domestic hot-water systems, we recommend to keep the liquid
temperature below +65 °C to eliminate the risk of lime
precipitation.
System pressure
The maximum permissible system pressure is stated on the pump
nameplate:
PN 6: 6 bar / 0.6 MPa
PN 10: 10 bar / 1.0 MPa
PN 16: 16 bar / 1.6 MPa.
Inlet pressure
Recommended inlet pressures:
Single-head pumps:
Min. 0.10 bar / 0.01 MPa at +75 °C
Min. 0.35 bar / 0.035 MPa at +95 °C
Min. 0.65 bar / 0.065 MPa at +110 °C.
Twin-head pumps:
Min. 0.90 bar / 0.09 MPa at +75 °C
Min. 1.20 bar / 0.12 MPa at +95 °C
Min. 1.50 bar / 0.15 MPa at +110 °C.
EMC (electromagnetic compatibility)
EN 55014-1:2006, EN 55014-2:1998, EN 61800-3-3:2008 and
EN 61000-3-2:2006.
Sound pressure level
The sound pressure level of the pump is lower than 43 dB(A).
Leakage current
The pump mains filter will cause a discharge current to earth
during operation. I
< 3.5 mA.
leakage
Consumption when the pump is stopped
1 to 10 W, depending on activity, i.e. reading the display, use of
Grundfos GO Remote, interaction with modules, etc.
40
Input/output communication
External potential-free contact.
Contact load: 5 V, 10 mA.
Two digital inputs
Screened cable.
Loop resistance: Maximum 130 Ω.
4-20 mA (load: 150 Ω).
Analog input
0-10 VDC (load: 78 kΩ).
Internal potential-free changeover contact.
Maximum load: 250 V, 2 A, AC1.
Two relay outputs
Minimum load: 5 VDC, 20 mA.
Screened cable, depending on signal level.
cos φ
The MAGNA3 has a built-in active PFC (Power Factor Control)
which gives a cos φ from 0.98 to 0.99, i.e. very close to 1.

19. Disposal

This product has been designed with focus on the disposal and
recycling of materials. The following disposal values apply to all
variants of Grundfos MAGNA3 pumps:
minimum 85 % recycling
maximum 10 % incineration
maximum 5 % depositing.
Values in percent of total weight.
This product or parts of it must be disposed of in an
environmentally sound way according to local regulations.
Subject to alterations.