B – Functional test of the amplifier lines/output sums
including testing the respective assignment to the output lines.
OUT: 1
LINE: 1,2,3
Fig. 39 Amplifier at output OUT CH 1: connected to the output and to
the inputs AMP IN for zones/lines CH 1, 2 and 3
OUT: 2
LINE: 4
Fig. 40 Amplifier at output OUT CH 2: connected to the output and to
the input AMP IN for zone / line CH 4
OUT: 3
LINE:
Fig. 41 Amplifier at output OUT CH 3: not connected
OUT: 4
LINE:
Fig. 42 Amplifier at output OUT CH 4: not connected
SPARE AMP
INSTALLED
Fig. 43 Spare amplifier at output OUT SPARE: connected to the output
and to the input SPARE AMP IN
C – Testing the output lines
LINE: 1
VALUE:A:015 B:025
Fig. 44 Speaker lines 1A and 1B
LINE: 2
VALUE:A:017 B:025
Fig. 45 Speaker lines 2A and 2B
LINE: 3
VALUE:A:000 B:000
Fig. 46 Speaker lines 3A and 3B not connected
LINE: 4
VALUE:A:000 B:000
Fig. 47 Speaker lines 4A and 4B not connected
D – Testing the battery voltage of the emergency power supply
BATT VOLTAGE:
INSTALLED
Fig. 48 Emergency power supply
E – Lines for fireman's microphones
FIRE MIC1
NOT INSTALLED
Fig. 49 Input FIRE MIC (30) on the rear side
5,0 V: no microphone connected or microphone line interrupted
3,3 V: connected microphone working
2,5 V: connected microphone activated
0 V:
short circuit on the microphone line
FIRE MIC1 COIL: 098
NOT INSTALLED
Fig. 50 Input FIRE MIC (30) on the rear side
170
25V
5,0V
 check microphone!
 check microphone line!
FIRE MIC2
INSTALLED
Fig. 51 Input FIREMIC (1) on the front side
5,0 V: no microphone connected or microphone line interrupted
3,3 V: connected microphone working
2,5 V: connected microphone activated
0 V:
short circuit on the microphone line
FIRE MIC2 COIL: 018
INSTALLED
Fig. 52 Input FIREMIC (1) on the front side
When the installation run has been successfully completed, the
following message will appear:
ZONE 1
:MUSIC 1
SYSTEM: OK
Fig. 53 Idle state
IMPORTANT Always perform an installation run after
including additional units or detectors or after replacing
components!
6.2 Display indications during
the reproduction of sources
When specific sources are activated, the following messages
will be displayed. These messages are independent from any
system error messages that may appear. Thus, the activation /
usage of the following sources will result in the following
messages:
FIRE MIC2
1234
SYSTEM: OK
Fig. 54 Announcement via the fireman's microphone connected to the
front side to AF outputs / zones 1, 2, 3 and 4
03 ALARM
1234
RED BUTTON: STOP
Fig. 55 The MP3 file "ALARM" is being reproduced via AF outputs / zones
1, 2, 3 and 4, triggered by the contact EMY 1 (26).
05 TEXT
13
SYSTEM: OK
Fig. 56 The MP3 file "TEXT" is being reproduced via AF outputs / zones
1 and 3, triggered by the contact MSG (29).
AUX
24
SYSTEM: OK
Fig. 57 A signal available at the AUX input is being reproduced via
AF outputs / zones 2 and 4, switched through via the contact
AUX (28).
SYS 4/2
34
SYSTEM: OK
Fig. 58 Announcement from a system microphone is being reproduced
via AF outputs/zones 3 and 4.
3,3V
 check microphone!
 check microphone line!
MEVAC4
MEVAC4
MEVAC4
MEVAC4
MEVAC4
35