03 ALARM
1234
RED BUTTON: STOP
Fig. 26 Display message when the ALARM text is being reproduced
ALARM STOPPED !!!
RED BUTTON: START
Fig. 27 Display message when the ALARM announcement has been
stopped with the button PROGRAM

5.6 Connecting the power supply unit

To ensure smooth operation even when the 230 V mains power
supply fails, MEVAC-4 provides a terminal for the connection
of a 24 V emergency power supply unit (39).
OUT
OUT
OUT
OUT
OUT
IN
SPARE
CH1
CH2
CH3
CH4
PRG
Fig. 28 Terminal for connection of a 24 V emergency power supply unit
The 24 V DC voltage must be continuously available at this
terminal; otherwise, the terminal cannot be monitored by
MEVAC-4. MEVAC-4 requires a current of approx. 600 mA.

5.7 Connection example

MEVAC-4PTT
MEVAC-1FT
MICRO-
FIRE-
MEVAC-4
PHONE
MIC
SINUS-20
Line
In
SINUS-20
Line
In
4 × 100-V-Endverstärker
4 × 100 V power amplifier
SINUS-20
Line
In
SINUS-20
Line
In
SINUS-20
Line
In
Reserve-100-V-Endverstärker
Spare 100 V power amplifier
ON/OFF
IN
24VDC
USE ONLY WITH A 250V FUSE
+ −
AUX
39
SMC-1
Line mono
IN
PRG
Relais in der MEVAC-4 eingebaut
Relays built into MEVAC-4
24 V
CH1
AMP IN
100 V
24 V
CH2
AMP IN
100 V
24 V
CH3
AMP IN
100 V
24 V
CH4
AMP IN
100 V
24 V
SPARE
AMP IN
100 V
24 V
This current will always be available when the emergency
power supply EVA-24 / 54 (approved according to EN54-4)
from MONACOR is used. With EVA-24 / 54, output 7, 8 or 9
(each 3 A max.) is used for connection to the terminal (39) of
MEVAC-4. The other two outputs are then available to supply
power to the priority relays for volume attenuators (also see
chapter 4.2.6).
7
8
9
Fig. 29 24 V outputs of EVA-24 /54
If you want to use the lower-priced PA-24ESP (not approved ac-
cording to EN-54-4), connect MEVAC-4 to the jack (1 A max.!)
shown in fig. 30, located on the rear side of PA-24ESP. The
"normal" 24 V outputs of PA-24ESP will be switched off as
long as mains voltage is available.
+24 V
GND
4
1
Fig. 30 24 V emergency power supply with PA-24ESP
positive pole (+) to pin 3, negative pole (−) to pin 1
PA-24RCD
Line stereo
CH1
LINE OUT
A
CH1
LINE OUT
B
CH2
LINE OUT
A
CH2
LINE OUT
B
CH3
LINE OUT
A
CH3
LINE OUT
B
CH4
LINE OUT
A
CH4
LINE OUT
B
EVA-24/54 + 2 × AKKU-12/120 + EVA-24CON
24 V
Hintergrundmusik
Background music
ESP-50EN/WS
ESP-224ABC
ESP-62/WS
24-V-Notstromversorung
24 V emergency power supply
IT-32EN