Herunterladen Inhalt Inhalt Diese Seite drucken

Electrical Connection; S32 Connector And Cable Connection; Shielding And Cable Routing - Balluff BTL7-P511-M Serie Betriebsanleitung

Magnetostriktives positionsmesssystem
Vorschau ausblenden Andere Handbücher für BTL7-P511-M Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
BTL7-P511-M _ _ _ _ -T _ 2/3-S32/KA _ _ /FA _ _
Magnetostrictive Linear Position Sensor – Rod Style
4
Installation and connection (continued)
Magnet
(e.g. BTL-P-1028-15R)
Supporting rod made of
non-magnetizable material
Fig. 4-9:
Example 2, BTL installed with supporting rod (only for
BTL7...-TB/TZ...)
4.4

Electrical Connection

Depending on the model, the electrical connection is made
using a cable or a connector.
The connection or pin assignments for the respective
version can be found in Tab. 4-2.
Note the information on shielding and cable
routing in section 4.5.
4.4.1

S32 connector and cable connection

Pin
Wire color
1
YE Yellow
2
GY Gray
3
PK Pink
4
RD Red
5
GN Green
6
BU Blue
7
BN Brown
8
WH White
Tab. 4-2:
Pin assignments for BTL7
Fig. 4-10: Pin assignment of S32 (view from above on BTL), 8-pin
M16 circular plug
www.balluff.com
BTL7-P511-...
+Init
+Start/Stop
–Init
Must remain free
–Start/Stop
GND
10...30 V
Must remain free
4.5

Shielding and cable routing

Defined ground!
The BTL and the control cabinet must be at the
same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect BTL and controller using a shielded cable.
Shielding: Braided copper shield with minimum 85%
coverage.
Connector version: Shield is internally connected to
connector housing.
Cable version: On the BTL side the cable shielding is
connected to the housing.
Ground the cable shielding on the controller side
(connect with the protective earth conductor).
Magnetic fields
The position measuring system is a magnetostrictive
system.
Ensure that there is sufficient distance between the BTL,
holding cylinder and strong, external magnetic fields.
Cable routing
Do not route the cable between the BTL, controller, and
power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
Cable length
BTL7-P...
Max. 500 m
Prerequisite: Construction, shielding and routing preclude the effect of any
1)
external noise fields. Required cable cross-section ≥ 0.6 mm
≤ AWG19.
Tab. 4-3:
Cable length BTL7
1)
2
and
english
11

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Btl7 -tk serie

Inhaltsverzeichnis