Herunterladen Inhalt Inhalt Diese Seite drucken

Photocells - V2 CITY1-EVO Bedienungsanleitung

Digitale steuerung für flügel- und schiebetore
Vorschau ausblenden Andere Handbücher für CITY1-EVO:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 154

5.5 - PHOTOCELLS

The control unit considers two kinds of photocells, depending on
the terminal to which they are connected:
Photocell 1
Photocells installed on the gate inner side, which are active both
during the opening and the closing phase.
When photocells 1 operate, the control unit stops the gate; as
soon as the photocell beam is free, the control unit will open the
gate completely.
m
WARNING: Type 1 photocells must be installed so that
they completely cover the opening area of the gate.
Photocell 2
Photocells installed on the external gate side and which are active
during the closing phase only.
When photocells 2 operate, the control unit opens the gate
immediately, without waiting for release.
The control unit supplies a 24Vac power supply to photocells and
it can perform a photocell operation test before starting the gate
opening phase.
NOTE: Photocell power terminals are protected by an electronic
fuse that stops current in case of overload.
L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11
FOT1
FOT2
RX
m
WARNING: the sensor cables must not be run in the
same conduit as the motor cables.
• Connect power supply cables of photocells transmitter
between terminals Z3 and Z2 of the control unit.
• Connect power supply cables of photocells receiver between
terminals Z1 and Z2 of the control unit.
• Connect the N.C. exit of the photocell receivers of the 1 type
between terminal boxes L7 and L11
C
To activate the functions, change the
settings
• Connect the N.C. exit of the photocell receivers of the 2 type
between terminal boxes L8 and L11
C
Function is active in closing and with gate standing
(closed). To change the operation, set parameter
in the programming menu.
m
WARNING:
• if several couples of same kind photocells are mounted, their
outputs must be connected in series.
• In case of reflection photocells, power supply must be
connected to terminals Z3 and Z2 of the control unit to carry
out the operation test.
Z1 Z2 Z3 Z4 Z5 Z6
- 38 -
Fot1
parameter
Fot2
TX

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis