1. Strip the PE conductor to a suitable length using a
pair of wire strippers.
2. Insert the bare conductor into the crimping cable
lug and crimp it with a crimping tool..
3. Tighten the crimp cable lug and the hexagon socket
screw M6 at the marked PE connection with a tight-
ening torque of 5 Nm.
REFUsol 50K-3T
982081 | 03 | 2021-03
(+3 mm)
(<2 mm)
(<1.5 mm)
4. If necessary, protect the PE connection against cor-
rosion.
4.9

Connect AC Cable

Tab. 5:
AC fuse and minimum cross-sections of the AC
cables
Type
Conductor cross section*
Fuse
* The conductor cross-sections shown in the table are minimum re-
quirements. For longer cable lengths, the conductor cross-sections
must be designed accordingly.
1. Open the connection box cover with an Allen key.
REFUsol 50K-3T
≥ 20 mm²
160 A