Tab. 8:
Event list with error and information messages
ID
Event name
Event description Measure
ID25
BusUVP
DC bus voltage is
too low.
ID26
BusOVP
DC bus voltage is
too high.
ID27
VbusUnbal-
DC bus voltage is
ance
unbalanced.
ID28
DciOCP
DC current is too
high.
ID29
SwOCPIn-
AC current is too
stant
high.
REFUsol 50K-3T
982081 | 03 | 2021-03
If the PV system configuration is correct (no ID05 error), the possible cause is insuf-
ficient solar irradiation. The inverter automatically returns to normal operating sta-
tus after the solar irradiation returns to a normal level.
ID26-ID27 are internal faults of the inverter, switch off the DC switch, wait 5 minutes
and switch on the DC switch again.
Check the DC voltages on both MPPT inputs and on the display. If no troubleshooting
is possible, contact REFU Service.
Check if the MPPT mode (parallel or independent) is set correctly according to the PV
system configuration, change if necessary.
When the correct MPPT mode is set, switch off the DC switch, wait 5 minutes and
switch on the DC switch again. If no troubleshooting is possible, contact REFU Service
.
Internal error of the inverter. Switch off the DC switch, wait 5 minutes and switch the
DC switch on again. If no troubleshooting is possible, contact REFU Service.
Error Messages and Troubleshooting
Main Menu (v2.6)
55