Tab. 8:
Event list with error and information messages
ID
Event name
Event description Measure
ID12
GFCIFault
GFCI error
ID13
GridFault
AC mains error
ID14
HwBoos-
The DC current is
tOCP
too high, the hard-
ware protection is
active.
REFUsol 50K-3T
982081 | 03 | 2021-03
If the insulation fault occurs frequently and lasts for a long time, the insulation resist-
ance of the PV system must be checked; possible causes of the fault could be defec-
tive PV cables or MC4 connections.
If this error occurs frequently, check the measured values of the AC network (fre-
quency, voltage, current) on the display.
Check that the DC current is within the maximum limits and check the connection to
the MPPT inputs. If no troubleshooting is possible, contact REFU Service.
Error Messages and Troubleshooting