Event list with error and information messages
Tab. 8:
ID
Event name
Event description Measure
ID52
Consist-
The comparison of
entFault_G-
the insulation
FCI
measurement val-
ues (GFCI) be-
tween master DSP
and slave DSP is
not consistent -
failed.
ID53
Spi-
SPI communica-
CommLose
tion between the
master DSP and
the slave DSP is
faulty.
ID54
Sci-
SCI communica-
CommLose
tion between the
master DSP and
the slave DSP is
faulty.
ID55
RelayTest-
Faulty AC relay
Fail
detected.
ID56
PvIsoFault
The insulation re-
sistance is too low.
58
Error Messages and Troubleshooting
Main Menu (v2.6)
ID49-ID55 are internal faults of the inverter, switch off the DC switch, wait 5 minutes
and switch on the DC switch again. If no troubleshooting is possible, contact REFU
Service.
If the insulation fault occurs frequently and lasts for a long time, the insulation resist-
ance of the PV system must be checked; possible causes of the fault could be defec-
tive PV cables or MC4 connections.