NOTICE
Risk of damage to the sensor tip:
Do not insert the sensor too far.
9 →
230
9
220
210
8
200
190
180
7
t-mass 300: Set the scale to the
calculated insertion depth.
12 →
90°(±3°)
t-mass 500-digital: Check and
ensure that the sensor on the
pipe is aligned at a 90° angle to
the direction of flow.
The arrow engraved on the
sensor shaft must match the flow
direction.
Align the scale to the pipe axis.
Endress+Hauser
10 →
230
9
220
210
8
200
190
180
7
t-mass 500-digital: Set the scale
to the calculated insertion depth.
13
36 mm
Tighten the coupling nut by hand.
Mounting for the first time:
Tighten coupling nut with 1 ¼
turns.
Repeat mounting: Tighten
coupling nut with 1 turn.
NOTE!  If strong vibrations can
be expected, tighten the coupling
nut with 1½ turns when
mounting for the first time.
11 →
90°(±3°)
t-mass 300: Check and ensure
that the sensor on the pipe is
aligned at a 90° angle to the
direction of flow.
The arrow engraved on the
sensor shaft must match the flow
direction.
Align the scale to the pipe axis.
EA01288D
15