Step 3: Drill wall hole for connective piping
1. Determine the location of the wall hole based
on the position of the mounting plate. Refer
to Mounting Plate Dimensions.
2. Using a 65mm (2.5in) or 90mm(3.54in)
(depending on models )core drill, drill a
hole in the wall. Make sure that the hole
is drilled at a slight downward angle, so
that the outdoor end of the hole is lower
than the indoor end by about 5mm to 7mm
(0.2-0.275in). This will ensure proper water
drainage.
3. Place the protective wall cuff in the hole. This
protects the edges of the hole and will help
seal it when you nish the installation process.
NOTE: When the gas side connective pipe is
16mm(5/8in) or more, the wall hole should be
Φ
90mm(3.54in).
Φ
CAUTION
When drilling the wall hole, make sure to
avoid wires, plumbing, and other sensitive
components.
Wall
Indoor
Outdoor
Fig.3.2
MOUNTING PLATE DIMENSIONS
Different models have different mounting plates.
For the different customization requirements, the
shape of the mounting plate may be slightly
different. But the installation dimensions are the
same for the same size of indoor unit.
Correct orientation of Mounting Plate
130mm(5.1in)
127mm(5in)
Left rear wall
hole 65mm (2.5in)
897mm(35.3in)
144mm(5.6in)
127mm(5in)
Left rear wall
hole 65mm (2.5in)
1004mm(39.5in)
450mm(17.7in)
89mm(3.5in)
Indoor unit
outline
Right rear wall
216mm
47mm
hole 65mm (2.5in)
(8.5in)
(1.8in)
Model A
518mm(20.4in)
83mm(3.2in)
Indoor unit
outline
Right rear wall
210mm
47mm
hole 65mm (2.5in)
(8.2in)
(1.8in)
Model B