Herunterladen Inhalt Inhalt Diese Seite drucken

gefran 600 Bedienungsanleitung Seite 28

Vorschau ausblenden Andere Handbücher für 600:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 34
Downloaded from
www.Manualslib.com
Lin
s. 0 0
......
s. 3 2
s. 3 3
s. 3 4
s. 3 5
User
U.CA
calibration
(1)
The analog output in 20mA is calibrated with accuracy higher than 0.2 % f.s.; calibrate when
converting to 10V output.
(2)
In the absence of calibration, accuracy is higher than 1% f.s.; calibrate only if higher
accuracy is required.
manuals search engine
• Lin
Custom linearization for main input
Step 0 beginning
Display limits
of scale value
(-1999...9999)
the n step value corresponds to input:
mV beginning scale + n*∆mV
∆mV = (mV full scale - mV beginning scale) / 32
Step 32
Display limits
full of scale value
(-1999...9999)
Step 33
mV beginning scale
Step 34
mV full scale
Step 35
mV at 50°C
• U.CAL
Val
Function
1
Analogue output
(1)
2
Input 1 – custom 10V / 20mA
3
Input 1 - custom 60mV
4
Custom PT100 / J PT100
5
Custom PTC
6
Custom NTC
7
Input 2 - custom TA
(2)
28
Only for TYP = Tc custom