Herunterladen Inhalt Inhalt Diese Seite drucken

Control Actions; Manual Tuning - gefran 600 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für 600:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 34
Proportional Action:
action in which contribution to output is proportional to deviation at input (deviation = difference between controlled variable and setpoint).
Derivative Action:
action in which contribution to output is proportional to rate of variation input deviation.
Integral Action:
action in which contribution to output is proportional to integral of time of input deviation.
* An increase in P.B. reduces oscillations but increases deviation.
* A reduction in P.B. reduces the deviation but provokes oscillations of the controlled variable (the system tends to be unstable if P.B. value is
too low).
* An increase in Derivative Action corresponds to an increase in Derivative Time, reduces deviation and prevents oscillation up to a critical
value of Derivative Time, beyond which deviation increases and prolonged oscillations occur.
* An increase in Integral Action corresponds to a reduction in Integral Time, and tends to eliminate deviation between the controlled variable
and the setpoint when the system is running at rated speed.
If the Integral Time value is too long (Weak integral action), deviation between the controlled variable and the setpoint may persist.
Contact GEFRAN for more information on control actions.
A) Enter the setpoint at its working value.
B) Set the proportional band at 0.1% (with on-off type setting).
C) Switch to automatic and observe the behavior of the variable. It will be similar to that in the figure:
Process
Variable
Peak
SP
SP1
IN1
LOC/REM
How to switch the unit OFF: hold down the "F" and "Raise" keys simultaneously for 5 seconds to deactivate the unit, which will go to the OFF
state while keeping the line supply connected and keeping the process value displayed. The SV display is OFF.
All outputs (alarms and controls) are OFF (logic level 0, relays de-energized) and all unit functions are disabled except the switch-on function
and digital communication.
How to switch the unit ON: hold down the "F" key for 5 seconds and the unit will switch OFF to ON. If there is a power failure during the OFF
state, the unit will remain in OFF state at the next power-up (ON/OFF state is memorized).
The function is normally enabled, but can be disabled by setting the parameter Prot = Prot +16. This function can be assigned to a digital input
(d.i.G) and excludes deactivation from the keyboard.
Downloaded from
www.Manualslib.com
8 • CONTROL ACTIONS
Influence of Proportional, Derivative and Integral actions on response of process under control
T
Time
10 • MULTISET FUNCTION, SET GRADIENT
SP2
SP1
(*)
SPrem
ON
ON
(*) if the set gradient is
set
11 • SOFTWARE ON / OFF SWITCHING FUNCTION
manuals search engine
9 • MANUAL TUNING
D) The PID parameters are calculated s follows: Proportional band
Peak
P.B.= ---------------------------------------- x 100
(V max - V min)
(V max - V min) is the scale range.
Integral time: It = 1.5 x T
Derivative time: dt = It/4
E) Switch the unit to manual, set the calculated parameters. Return to PID action by setting
the appropriate relay output cycle time, and switch back to Automatic.
F) If possible, to optimize parameters, change the setpoint and check temporary response.
If an oscillation persists, increase the proportional band. If the response is too slow, reduce
it.
The multiset function is enabled in hd.1.
The gradient function is always enabled.
You can select between setpoint 1 and setpoint 2 with the faceplate key or
with digital input.
You can display the setpoint 1-2 selection by means of LED.
SET GRADIENT: if set to ≠0, the setpoint is assumed equal to PV at power-
on and auto/man switchover. With gradient set, it reaches the local setpoint
t
or the one selected.
Every variation in setpoint is subject to a gradient.
t
The set gradient is inhibited at power-on when self-tuning is engaged.
If the set gradient is set to ≠0, it is active even with variations of the local
setpoint, settable only on the relative SP menu.
t
The control setpoint reaches the set value at the speed defined by the
gradient.
30

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis