THE EASY CONFIGURATION IS SUITABLE FOR VERSIONS WITH
TWO OUTPUTS (OUT1, OUT2). TO ACCESS THE OTHER
PARAMETERS, ADD 128 TO THE Pro VALUE.
P.V. / S.V.
al. 1
h. p b
h. i t
h. d t
typ.
dp. s
lo. s
a1. t
(t. 2
Downloaded from
www.Manualslib.com
5 • "EASY" PROGRAMMING and CONFIGURATION
LEVEL 1 MENU
P.V. / S.V.
Process variable (PV display)
Work Setpoint (SV display) or control
output value with controller in manual
Alarm point 1 (scale points)
Proportional band
0 ... 999.9%
for heating or hysteresis
full scale
in regulation ON/OFF
Integral time
0.00 ... 99.99 min
for heating
Derivative time
0.00 ... 99.99 min
for heating
Probe type, signal, enable custom linearization, and main input
scale (See type table, page 6)
dP_S
Format
0
xxxx
Decimal point position for
1
xxx.x
main input scale
2
xx.xx
3
x.xxx
Minimum limit of main
min...max input range
input scale
selected in tyP
• Out
AL.1.t, AL.2.t, AL.3.t
AL.x.t
Direct (high limit)
Absolute
Alarm
Inverse (low limit)
or relative
type 1
to active setpoint
0
direct
absolute
1
inverse
absolute
2
direct
3
inverse
4
direct
absolute
5
inverse
absolute
6
direct
7
inverse
+ 8 to disable at power-on until first alarm
+ 16 to enable alarm memory
+ 32 Hys becomes delay time when alarm trips (0...999 sec.)
(excluding symmetrical absolute)
+ 64 Hys becomes delay time when alarm trips (0...999 min.)
(excluding symmetrical absolute)
Cycle time for
Out2
1...200 sec.
(Heat or Cool)
manuals search engine
S4 Jumper
(CPU)
ON
• CFG
h. p . x
Xy. i
• InP
xi. s
lo. l
xi. l
Normal
Symmetrical
Pro
(window)
normal
normal
relative
normal
relative
normal
symmetrical
symmetrical
relative
symmetrical
relative
symmetrical
20
CFG
Custom menu
InP
Input settings
Out
Output settings
PAS
Password
PAS = 99
Pro
Protection code
Maximum power limit
0.0 ... 100.0%
for heating
Alarm 1 hysteresis
±999 scale points
Maximum limit of main
min...max input range
input scale
selected in tyP
Lower limit for local
setpoint and absolute
Lo.S ... Hi.S
alarms
Upper limit for local
setpoint and absolute
Lo.S ... Hi.S
alarms
• Prot
Protection code
Prot
Display
0
SP, alarms
1
SP, alarms
2
SP
+ 4
to disable InP, Out
+ 8
to disable CFG
+128 enables full configuration
0...999 sec.
If +32 in A1.t
0...999 min.
If +64 in A1.t
Modification
SP, alarms