Herunterladen Inhalt Inhalt Diese Seite drucken

System Design; Connection To Video Matrix; Control Unit Connected To Simatrix Interface (Term.x) - Siemens CKA4820 Betriebsanleitung

Bediengerät
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5

System Design

5.1

Connection to Video Matrix

5.1.1

Control Unit Connected to SIMATRIX Interface (Term.x)

Siemens Building Technologies
Fire Safety & Security Products
As standard, the control unit interface of the CKA4820 is set as a TTY interface
(COM1B) for control of the SIMATRIX 164/648/SYS.
Connect control unit to SIMATRIX
Connect the CKA4820 to the terminal socket (Term.x) of the video matrix via the
control unit interface COM1B.
Fig. 6
Connection of Control Unit CKA4820 to a SIMATRIX interface (Term.x)
Required accessories
Control line: 4-core cable; max. permissible length approx. 1.2 km with 0.8 mm
conductor diameter.
9-pin Sub-D plug with housing.
9-pin Sub-D socket with housing.
With the SIMATRIX 164/648, the internal power supply for the control unit is
possible via Term.1, and with the SIMATRIX SYS via Term.1 to 4. A 6-core cable
is required if the power supply is obtained from the SIMATRIX. Please note the
precut/preassembled cable in the Ordering data. With a cable length above 70 m
or if more than two control units are connected, the power supply must be provided
by a separate power supply unit on the control unit. It must be guaranteed that the
control unit is powered with DC 12 V +10 %, -15 % (SELV).
Term.x
COM2
System Design
SIMATRIX
TTY
12 V
200 mA
COM1B
COM1A
Power
supply unit
69
01.2005

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis