Siemens Building Technologies
Fire Safety & Security Products
The Control Unit CKA4820 is delivered with the factory settings described below.
Section 4.3 describes the individual functions of the DIP switches and the
corresponding assignment to the interfaces.
OFF
3
6
OFF
3
6
SW401
Fig. 4
Default settings of DIP switches in Control Unit CKA4820 (side view)
The white area identifies the switch position. White at the bottom means ON.
DIP switch SW401: switches 3, 6 at bottom
TTY interface (COM1B)
DIP switch SW301: switches 1, 3, 5, 6, 8 at bottom
RS485 interface (COM2)
Terminating resistor: ON
Audible signal transmitter: ON
DIP switches SW1, SW2: all switches at top
(Changing of switch positions will cause malfunctioning !)
DIP
DIP
OFF
OFF
1
3 5
6
8
SW301
SW2
RS485/19200 Bd
SIVIS-DOME protocol
Terminating resistor ON
COM2
Design of CKA4820
OFF
1
3 5
6
8
DIP
OFF
SW1
TTY/2400 Bd
COM1B
COM1A
12 V
200 mA
67
01.2005