ATTENTION! The relevant standards must be observed.
For use below the backwash level:
Guide the discharge line with a loop above the backwash level.
>
>
If the base of the discharge line loop is more than 5 m above the lifting unit, an
additional checkvalve must be installed.
>
Provide shut off valves.
>
Every drain must be fitted with an odour trap.
Also see installation dimensions (chapter 20, page 44 - 45, figure 14).
ATTENTION!
>
The set up must be made frost-free and on level ground.
Connection of discharge pipe
>
Use a PVC discharge pipe with an outside diameter of 25 or 32 mm.
>
Push the pipe to about 16 mm into the rubber sleeve (use a lubricant if necessary)
and secure it on the outside with the existing hose clamp.