7. Maintenance, repair and cleaning
Replacing mica shields with model LGG-M
CAUTION!
Physical injuries and damage to property and the
environment
Mount the mica shields carefully.
▶
The mica shieds should not exhibit any chips or cracks on
the wetted side
▶
Observe the alignment of the label "Water side"
Threaded studs:
5901165344A for 50X2/60X2
5901165444A for 80X2/90X2
Depressurise the vessel
■
Close the lower and then the upper valve head
■
Open the drain valve and allow the media to drain
■
Loosen the nuts and lift up the pressure plate
■
Remove the pressure plate, the mica shield, loose sealing parts and
■
cushion
Clean the sealing face (do not use any sharp-edged tools)
■
Should the contact surfaces be damaged, they must be sent back to
■
the manufacturer for reconditioning
Insert a new sealing into the sealing face
■
Insert the mica shields (label "Water side" shows in the direction of
■
the liquid channel). Eventually place a spring sheet or cushion on the
mica shield package for thickness compensation.
Place the pressure plate over the mica shield and centre
■
Carry out the mounting as described in chapter 5.2 "Mounting of
■
models LGG-R, LGG-T, LGG-M"
Seat the cover back via the threaded studs
■
Carry out the leak test
■
Operating instructions glass level gauge, model LGG
Sealing
Nut:
D025108016
Pressure plate
Pressure frame
Mica shield or mica
bundle
21
EN