4.3.2
Pneumatic connection for 6DR5..5 and 6DR5..6
Structure
The pneumatic connections are provided on the right side of the positioner.
Restrictor Y2
*)
Restrictor Y1
Actuating pressure Y2
Supply air PZ
*) for double-acting actuators
Figure 4-15
Pneumatic connection in the flameproof enclosure
4.4
Restrictors
● Reduce the air output to achieve travel times of T > 1.5 s for small actuators. Use restrictors Y1
purpose.
● When turned clockwise, they reduce the air output and finally shut it off.
● In order to set the restrictors, we recommend closing them and then opening slowly.
● In case of double-acting valves, ensure that both restrictors have approximately the same setting.
Restrictor Y1
Restrictor Y2, only in the version for double-acting actuators
Hexagon socket-head screw 2.5 mm
Figure 4-16
Restrictors
30
*)
Actuating pressure Y1
Exhaust air outlet
Enclosure ventilation (2x)
and Y2
for this
SIPART PS2 (6DR5...)
A5E03436620-07, 10/2015