Mechanical limit switch modules 6DR4004-6K and -8K
Supply with hazardous voltage
DANGER
Supply with hazardous voltage
When you supply the non-intrinsically safe version of the module with hazardous voltage, you must read the following
safety rules before starting work on the device:
1. Isolate the device from power. Use a circuit breaker positioned near the device to do this.
2. Make sure that the device cannot be switched back on inadvertently.
3. Make sure the device is truly isolated from power.
CAUTION
Maximum AC/DC switching voltage with UL approval E344532
The mechanical limit switch module 6DR4004-6K is approved for use for positioners with UL approval. The maximum
supply voltage in this case is 30 V AC/DC.
The mechanical limit switch module 6DR4004-8K is not approved for use for positioners with UL approval.
If this information is ignored, the UL approval for the mechanical limit switch module for the positioner becomes invalid.
Non-hazardous area
Hazardous area
Mechanical limit switch module
Fault message
Figure 4-12
Mechanical limit switch module
Procedure
1. Loosen the screw
2. Pull the transparent cover
3. Tighten every cable in the corresponding terminal.
4. Slide the transparent cover
5. Tighten the screw
SIPART PS2 (6DR5...)
A5E03436620-07, 10/2015
on the transparent cover
up to the front end stop.
up to the end stop of the basic electronics.
of the transparent cover
Limit
Switching amplifier
Switching output
.
.
25