The rear steel panel of the NCS sensor is inevitably bonded to the ground potential of the system when mounting on the
console. This ground connection is only functional if there is a low-impedance connection to ground potential of the
system. Ensure this state by measuring the ground resistance. If necessary, ensure proper grounding by means of an
additional cable from the NCS sensor to ground potential.
4.2.6
Connecting the external position detection system to the EMC filter module
Requirement
You need the EMC filter module with article number C73451-A430-D23 for the electrical connection of an external position
detection system, article number C73451-A430-D78, to the positioner.
Wiring diagram
EMC filter module terminals
Positioner with integral EMC filter module C73451-
A430-D23
Yellow wheel for locking the position detection
Ribbon cable connector of fitted potentiometer, or
ribbon cable connector of EMC filter module
Basic electronics
Screw
EMC filter module C73451-A430-D23
Figure 4-8
Connection to positioner
SIPART PS2 (6DR5...)
A5E03436620-07, 10/2015
External position detection system C73451-A430-
D78
External position detection system terminals
External position detection system cable gland
Cable
EMC filter module cable gland
Input signal for positioner