WARNING
Unprotected cable ends
Danger of explosion through unprotected cable ends in hazardous areas.
Protect unused cable ends in accordance with IEC/EN 60079-14.
WARNING
Improper laying of shielded cables
Danger of explosion through compensating currents between hazardous area and the non-hazardous area.
Only ground shielded cables that run into the hazardous area at one end.
If grounding is required at both ends, use an equipotential bonding conductor.
WARNING
Unsuitable cables and/or cable glands
Danger of explosion in hazardous areas.
Only use suitable cables and cable glands complying with the requirements specified in Chapter "Technical data
(Page 43)".
Tighten the cable glands in accordance with the torques specified in Chapter "Technical data (Page 44)".
When replacing cable glands use only cable glands of the same type.
After installation check that the cables are seated firmly.
WARNING
Incorrect selection of type of protection
Danger of explosion in areas subject to explosion hazard.
This device is approved for several types of protection.
1. Decide in favor of one type of protection.
2. Connect the device in accordance with the selected type of protection.
3. In order to avoid incorrect use at a later point, make the types of protection that are not used permanently
unrecognizable on the nameplate.
NOTICE
Condensation in the device
Damage to device through formation of condensation if the temperature difference between transportation or storage and
the mounting location exceeds 20 °C (36 °F).
Before taking the device into operation let the device adapt for several hours in the new environment.
NOTICE
Ambient temperature too high
Damage to cable sheath.
At an ambient temperature ≥ 60 °C (140 °F), use heat-resistant cables suitable for an ambient temperature at least
20 °C (36 °F) higher.
NOTICE
Standard cable gland/torque
Device damage.
Owing the reasons pertaining to tightness (IP enclosure rating) and the required tensile strength, only use the cables
having a diameter ≥ 8 mm for standard M20x1.5 cable gland, or use a suitable seal insert in case of smaller diameters.
In the NPT version, the positioner is delivered with a coupling. When inserting a counter piece in the coupling, ensure
that the maximum permissible torque of 10 Nm is not exceeded.
SIPART PS2 (6DR5...)
A5E03436620-07, 10/2015
15