5. Electrical data

5.1 Inputs

Digital inputs
Data:
Voltage category
Insulation voltage
Insulation test voltage
Input filter time
Digital inputs 5 to 7:
Output voltage
(open contact)
Output current
(closed contact)
Pulse counter input (DI8):
Max. frequency
Output voltage
(open contact)
Output current
(closed contact)
The digital inputs are activated by short-circuiting the
input concerned to 0 V, e.g. with a contact or a relay.
The pulse counter input, digital inputs and analog
inputs have the same minus potential. The inputs are
not isolated from each other.
10
II
50 V
(to system earth)
700 VDC
41 ±7 ms
24 V, internal 4.7 kΩ
pull-up
5 mA
10 kHz
5 V, internal 1 kΩ
pull-up
5 mA
Analog inputs
Voltage input:
Voltage category
Insulation voltage
Insulation test voltage
Input band width
Mains frequency
suppression
Voltage range, optional
Input resistance
Input resolution
Tolerance at 25°C
Current input:
Current range, optional
Input resistance
Input resolution
Tolerance
Filter times:
Integration time
Reading interval

5.2 Outputs

Relay outputs
Data:
Voltage category
Insulation voltage
Insulation test voltage
Insulation between
two channels
Max. connection voltage
Max. load
Min. load
Max. load power AC/DC
II
50 V
(to system earth)
700 VDC
10 Hz, second order
filter
50-60 Hz
(to be set up)
0-10 V
2-10 V
250 kΩ
2.4 mV
0.1%
0-20 mA
4-20 mA
250 Ω
5 µA
±0.1%
40 ms
160 ms
III
400 V
(to system earth)
4 kVAC
2.6 kVAC
400 VAC
400 VAC, 2 A, AC-15/
24 VDC, 2 A, DC-13
5 V/10 mA
400 VA/48 W

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis