Purging the appliance

Place a tray under the purge
pipe to collect the water.
2
Take a flat screwdriver.
Loosen slightly (1/4 turn) to
purge the air until the water
arrives, then tighten again.

7/ Setting the water temperature from the heat pump

Weather dependent setpoint
The operation of the heat pump is controlled by a weather dependent setpoint.
The setpoint temperature of the heating / cooling water circuit is adjusted according to the outside temperature.
The weather dependent setpoint must be manually set by the installer, following these instructions.
Heating mode
Manual setting of the weather dependent setpoint
The weather dependent setpoint gradient determines the impact of the outside temperature variations on the variations
of the heating's initial temperature.
The steeper the gradient, the greater the rise in the water temperature in the heating circuit when the outside tempera-
ture drops.
The graph below shows different weather dependent setpoints that are recommended for a Dynamic Radiator, depending
on the type of building (New or Renovation) :
65
60
55
50
45
40
35
30
25
20
20
Please set the heating circuit's minimum initial temperature in the Dynamic Radiator area to:
- 30°C for a building in compliance with the Thermal Regulation RT 2012;
- 35°C for all other buildings.
Refer to the heat pump's manual to enter the values for the graph and the type of home.
15
10
5
Outside temperature (°C)
0
-5
-10
14
Weather
dependent
setpoint gradients
1,05
0,90
RENO.
0,75
0,60
NEW
0,45
-15
-20