11. Shut down of Electric Power Generator Unit
1.
Switch off the electric power consumers and disconnect them from the electric power generator unit.
2.
Let the engine operate without load for about 5 minutes.
3.
Turn the lock key into the «•» position.
4.
Emergency stop - If this button is pressed, the engine stop valve acts instantly and the engine stops.
12. Possible faults and ways of their elimination
No.
Faults
1
The engine can not be started
2
The gas-electric generating set
can not be started
tilting or falling of the aggregate)
3
The gas-electric generating set
does not deliver enough voltage
4
No or not enough voltage
after loading
is not serviceable
5
Excessive voltage of the gas-electric
6
Generator gets inadmissible warm
Origin
Not enough oil is filled or
the gas-electric generating set is
situated on an inclined ground
Engine oil in the combustion
chamber (because of intensive
Overcurrent circuit breaker
is actuated or defect
Insufficient rotation speed
of the engine
The air filter and/or the
carburettor is contaminated
Insufficient rotation speed of the
engine or the speed controller
max. 250 Volt in an authorized workshop
Climatic influences reduce
the power of the gas-electric generating set
Excessive speed of the engine generating set
Overloading of the gas-electric generating set
Power reduction because of situating in the height
Excessive environment temp.
Generator air intake is blocked.
Elimination
Check the oil level, if necessary
refill the engine oil or provide
an even surface
Remove the spark plug and
pull through the engine with a reversing starter 3-4 times.
Clean the carburettor and the air filter.
Actuate or replace the circuit
breaker
run up to rated speed, idle
running 51 Hz, max. 240 V
Clean the component or insert
a new filter set
The engine must be set to the
rated speed of 51 Hz
Do not load the gas-electric
generating set with the rated speed, see operating instructions of the engine
Adjust to 230 Volt
Switch off some consumers
Only partial loading possible
The gas-electric generating sets are designed for an environment temperature up to 40°C
The air intake must be unobstructed for effective cooling.
20
12.2006