6.4
Disposal
7

Technical data

7.1
All device versions
7.1.1

Operating conditions

Ambient temperature
● Permissible ambient temperature for operation
Degree of protection
1)
Mounting position
Vibration resistance
● Harmonic vibrations (sine) according to DIN EN 60068-2-
6/05.96
● Bump (half-sine) according to DIN EN 60068-2-29/03.95
● Noise (controlled digitally) according to DIN EN 60068-2-
64/08.95
● Recommended range of continuous operation of the entire
control valve
Climate class
● Storage
● Transport
● Operation
2)
Impact energy max. 1 joule for enclosures with inspection window 6DR5..0and 6DR5..1.
1)
At ≤ -10 °C (≤ 14 °F), the display refresh rate of the display is limited. When using Iy module, only T4 is permissible.
2)
-20 ... +80 °C (-4 ... +176 °F)for 6DR55..-0G..., 6DR56..-0G..., 6DR55..-0D...and 6DR56..-0D...
3)
See also
Certificates, approvals, explosion protection (Page 37)
7.1.2

Pneumatic data

Auxiliary power (air supply)
● Pressure
Air quality in accordance with ISO 8573-1
● Solid particulate size and density
SIPART PS2 (6DR5...)
A5E03436620-02, 01/2013
Devices identified by this symbol may not be disposed of in the municipal
waste disposal services under observance of the Directive 2002/96/EC on
waste electronic and electrical equipment (WEEE).
They can be returned to the supplier within the EC or to a locally approved
disposal service. Observe the specific regulations valid in your country.
In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
-30 ... +80 °C (-22 ... +176°F)
IP66 according to EN 60529 / NEMA 4X
Any; in wet environment, pneumatic connections and
outlet opening not upward
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axes
98.1 m/s² (321.84 ft/s²), 27 to 300 Hz, 3 cycles/axes
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axle
10 to 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 to 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axle
≤ 30 m/s² (98.4 ft/s²) without resonance peak
According to DIN EN 60721-3-4
1K5, but -40 ... +80°C (1K5, but -40 ... +176°F)
2K4, but -40 ... +80°C (2K4, but -40 ... +176°F)
4K3, but -30 to +80 °C (4K3, but -22 to +176 °F)
Compressed air, carbon dioxide (CO2), nitrogen (N), noble
gases or cleaned natural gas
1.4 to 7 bar (20.3 ... 101.5 psi)
Class 2