Types of initialization
You can initialize the positioner as follows:
● Automatic initialization:
during automatic initialization, the positioner determines the following one after the other:
– The direction of action
– The actuator travel and angle of rotation
– Movement times of the actuator
The positioner also adjusts the control parameters as per the dynamic response of the actuator.
● Manual initialization:
the actuator travel and the angle of rotation of the actuator are set manually. The remaining parameters are automatically
determined. This function is useful for actuators with soft end stops.
● Copying the initialization data when replacing a positioner:
the initialization data of a positioner can be read and copied into another positioner. A defective device can thus be
replaced without interrupting an ongoing process through initialization.
You have to define a few parameters for the positioner before initialization. Owing to the preset values, you cannot adjust
further parameters for initialization.
You can use a suitably configured and activated binary input to protect the configured settings against accidental
adjustment.
5.3

Sequence of automatic initialization

See detailed operating instructions for information on sequence of automatic initialization.
5.4
Parameter
5.4.1
Overview of parameters 1 to 5
Introduction
Parameters 1 to 5 are the same for all versions of positioner. These parameters are used to adjust the positioner to the
actuator. Normally the parameter setup is sufficient to be able to operate the positioner on an actuator.
If you want to get to know the positioner in detail, gradually try out the effects of the remaining parameters by systematic
testing
Note
Factory-set parameter values are printed in bold in the following table.
Overview
Parameter
Function
1.YFCT
Type of position actuator
2.YAGL
Nominal angle of rotation of the feedback message
26
Parameter values
turn (part-turn actuator)
WAY (linear actuator)
LWAY (linear actuator without sine correction)
ncSt (part-turn actuator with NCS)
-ncSt (part-turn actuator with NCS, inverse
direction of action)
ncSL (linear actuator with NCS)
ncSLL (linear actuator with NCS and lever)
1)
33°
90°
Unit
Degrees
SIPART PS2 (6DR5...)
A5E03436620-02, 01/2013