Herunterladen Inhalt Inhalt Diese Seite drucken

Siemens 6DR5 Serie Kompaktbetriebsanleitung Seite 9

Elektropneumatische stellungsregler
Vorschau ausblenden Andere Handbücher für 6DR5 Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 99
CAUTION
Unsuitable compressed air
Device damage. As a general rule, the positioner must only be operated with dry and clean compressed air.
● Use the customary water separators and filters. An additional dryer is required in extreme cases.
● Use dryers, especially if you operate the positioner at low ambient temperatures.
CAUTION
Prior to working on the control valve
Danger of injury.
● Before starting work on the control valve, move it into the safety position.
● Make sure that the control valve has reached the safety position.
● If you only interrupt the pneumatic auxiliary power to the positioner, it may be the case that the safety position is only
reached following a certain delay.
WARNING
Mechanical impact energy
Protect the 6DR5...0-.G...-.... version of the positioner from mechanical impact energy greater than 1 joule; this ensures
that the IP66 degree of protection is guaranteed.
When mounting, observe the following sequence imperatively to avoid injuries or mechanical damage to the
positioner/mounting kit:
1. Mount the positioner mechanically.
2. Connect the electrical auxiliary power supply.
3. Connect the pneumatic auxiliary power supply.
4. Commission the positioner.
NOTICE
Impact energy and torque
For versions 6DR5a.b-.Gc..-...., where a = 0, 2, 5, 6; b = 0, 1; c = G, N, M, P, Q, the following is applicable:
The device must be protected against power surges of over one joule.
For versions 6DR5a.b-.Gc..-...., where a = 0, 2, 5, 6; b = 0; c = G, N, M, P, Q, the following is applicable:
The maximum torque on the thread of the cable gland should not exceed 67 Nm.
3.1.1
Proper mounting
NOTICE
Incorrect mounting
The device can be damaged, destroyed, or its functionality impaired through improper mounting.
● Before installing ensure there is no visible damage to the device.
● Make sure that process connectors are clean, and suitable gaskets and glands are used.
● Mount the device using suitable tools. Refer to the information in Chapter "Constructional design (Page 36)", for
example installation torques requirements.
CAUTION
Loss of degree of protection
Damage to device if the enclosure is open or not properly closed. The degree of protection specified on the nameplate or in
Chapter "Technical data (Page 35)" is no longer guaranteed.
● Make sure that the device is securely closed.