1. Switch to the "Configuration" mode. To do this, press the
following:
2. Call the "2.YAGL" parameter. To do this, briefly press the
the setting:
3. Check whether the value displayed in the "2.YAGL" parameter matches the setting of the transmission ratio selector. If
required, change the setting of the transmission ratio selector to 33° or 90°.
4. Set the "3.WAY" parameter to determine the total stroke in mm. The setting of parameter 3 is optional. The display
shows the determined total stroke only at the end of the initialization phase.
– Briefly press the
parameter 4.
– Call the "3.YWAY" parameter. To do this, briefly press the
Note
Set the "3.YWAY" parameter
Proceed as follows to set parameter 3:
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter with the buttons or to the read value.
5. Call the "4.INITA" parameter. To do this, briefly press the
6. Start the initialization process. To do this, press the
The positioner runs through five initialization steps during the automatic initialization process. Displays for the
initialization steps from "RUN 1" to "RUN 5" are shown in the lower line on the display. The initialization process depends
on the actuator used, and takes up to 15 minutes.
SIPART PS2 (6DR5...)
A5E03436620-02, 01/2013
button if you do not require any information about the total stroke in mm. You are then directed to
button for at least 5 seconds. The display shows the
button. The following is shown on the display depending on
button. The display shows the following:
button. The display shows the following:
button for at least 5 seconds until the display shows the following: