Troubleshooting

5.2 Alarm Letter Codes and Descriptions

Message
Low Signal - Press <ENT>
Detection Fault
Note
If you receive a Detection Fault message, it is strongly recommended that the Technical
Service Department (http://www.automation.siemens.com/partner) be contacted.
5.2
Alarm Letter Codes and Descriptions
The following alarm codes appear on the main display of the transmitter.
Table 5-2
Alarm Codes and Descriptions
Letter Codes
Alarm Code
SPACE
Spacing
EMPTY
Empty
HI/LO
Rate
FAULT
Fault
AER
Aeration
MEMRY
Memory
MAKUP
Makeup
I
Interface
P
Pig
Z
ZeroMatic
34
Description
During the Initial Makeup the flowmeter decides that the level of the receive signal is
insufficient for proper operation. Some reasons for low signal are:
● Invoking [Install Complete] on an empty pipe.
● Coupling compound insufficient; not applied or evaporated.
● A disconnected or broken transducer cable.
● The pipe needs to be conditioned at the mounting location.
● Flush out large air bubbles.
● The sensor cables are defective or not connected to the correct channel.
● The Set Empty routine performed when pipe was NOT actually empty.
If you locate and correct the improper condition immediately, press <ENT> to resume the
installation procedure. Otherwise, press the <Left Arrow> to abort the installation and
conduct a thorough investigation.
If it appears that the flowmeter cannot complete an Initial Makeup it means that the pipe
and/or liquid conditions do not permit a receive signal that meets the flow detection
standards. The system will not operate.
Call technical support for help, if necessary.
Description
Sensor spacing may need adjustment
Pipe is empty
Flow above High setting or below Low setting
Three continuous seconds without new data update
Current aeration percentage exceeds the alarm set point
Last valid reading for a selected interval during Fault condition
In-Process Makeup occurred
The following alarm codes appear in the Datalogger status messages:
Liquid Vs exceeds interface alarm set point
Pig passage detected (optional)
ZeroMatic signal occurred
FUT1010 IP65 NEMA 4X & IP66 NEMA 7 Liquid Quick Start
Operating Instructions, 6/2010, A5E02639182A Revision 02