Herunterladen Inhalt Inhalt Diese Seite drucken

Figure 3-4 Temperature Sensor To Junction Box Wiring - Siemens SITRANS FUT1010 IP65 NEMA 4X Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für SITRANS FUT1010 IP65 NEMA 4X:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Connecting
3.1 Transmitter Wiring
Black
Orange
Brown
Red
Blue
Short Terminals 1 and 4
Figure 3-4
Temperature Sensor to Junction Box Wiring
Wiring Temperature Sensor Board
1. Using a flat-blade screwdriver, loosen Terminal Block TB1 and TB2 screws.
2. Wire the RTD 1012EC temperature cable as shown in the table below:
1012EC Series Cable
Wire #1 (Black)
Wire #2 (Orange)
Wire #3 (Brown)
Wire #4 (Red)
Wire #5 GND/SHLD (Blue)
3. Complete the temperature sensor current loop by shorting together terminals 1 and 4 of
4. Ground the voltage sensing leads (terminals 2 and 3 of TB2) by connecting them both to
24
the unused TB2 temperature sensor terminal block.
terminal 5.
Ground Terminals 2 and 3 to Terminal 5
1012EC Series Cable
Module 7ME39400SA00
Sensor Body Junction Box
Temperature Sensor Terminal Board TB1
Junction Box shown with cover removed
Terminal TB1
To TB1--1
To TB1--2
To TB1--3
To TB1--4
To TB1--5
FUT1010 IP65 NEMA 4X & IP66 NEMA 7 Liquid Quick Start
Operating Instructions, 6/2010, A5E02639182A Revision 02

Werbung

Kapitel

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Sitrans fut1010 ip66 nema 7Sitrans f 7me362

Inhaltsverzeichnis