5. Tighten all TB1 and TB2 terminal block screws.
6. Replace I/O Board and secure with four screws paying careful attention to pin alignment.
7. Replace Access Cover, tighten captive screw and close transmitter case.
Table 3-1
TB3 and TB4 Wiring
Pin
TB3 Function
1
AUX. 1 IN
2
AUX. 1 COM
3
AUX. 2 IN
4
AUX. 2 COM
Notes on Analog Input Modules
Dual Path Models
● All models use T1 to report temperature.
● The Analog Input of temperature takes priority over the built-in RTD (Resistive Thermal
3.2

Sensor Wiring

3.2.1

Connecting Sensor Cables to Sensor

Figure 3-5
FUT1010 IP65 NEMA 4X & IP66 NEMA 7 Liquid Quick Start
Operating Instructions, 6/2010, A5E02639182A Revision 02
Note
TB3 and TB4 are also active analog inputs. See wiring table below.
TB4 Function
Use
AUX. 3 IN
Iin1 Input
AUX. 3 COM
Iin1 Common
AUX. 4 IN
Iin2 Input
AUX. 4 COM
Iin2 Common
Device) measurement of temperature when provided.
Line Taps (1/4" and 3/4")
Sensor Pipe Section
Sensor Enclosures
Sensor Overview
Description
Behaviour
Analog current
4 to 20mA
input
referenced to
meter ground.
Junction Box
Upstream and Downstream I/O Cables
Connecting
3.2 Sensor Wiring
Load
Wiring
200Ω
1000 ft.
Max w/o
factory
approval
25