Slowing down time
In case this function is enabled, during the last seconds of motion, the
control unit will give motor a reduced power command, to avoid a
strong impact with the stop end. t.AP is the max. allowed time.
WARNING:
• In case the self-learning function of working times is NOT used, we
recommend disabling the slowing down function in order to
measure both opening and closing times, and to enable it again
once the setup has been carried out. The control unit will
automatically consider the working time delay caused by the
slowing down.
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the opening phase.
PAUSThe door stops and goes to pause
ChiU
The door immediately starts closing
no
The door go on with the opening phase (command is ignored)
Select option PAUS, to set up the "step-by-step" operation logic.
Select option 'no', to set up the 'always open' operation logic.
Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the closing phase.
StoP
The door stops and its cycle is considered as finished
APEr
The door opens again
Select option StoP, to set up the "step-by-step" operation logic.
Select option APEr, to set up the 'always open' operation logic.
Start command during the pause
This menu allows fixing the control unit conduct in case it receives a
Start command when the door is open during its pause phase.
ChiU
the door starts closing
no
command is ignored
Select option ChiU, to set up the "step-by-step" operation logic.
Select option 'no', to set up the 'always open' operation logic.
Apart from selected option, the start command lets the door close if it
has been stopped by a stop command or if the automatic closing was
not enabled.
Automatic closing
During the automatic operation, the control unit will automatically close
the door when a set-up time expires.
The Start command, if enabled by St.PA menu, allows closing the door
before the set up time expires.
In semi-automatic operation, that is to say, if the automatic closing
function is disabled by setting the value to zero ('no' will be displayed),
the door can be closed through the start command only: in this case,
St.PA menu setup will be ignored.
If the control unit receives a Stop command when the door is in
pause, it will automatically pass to the semi-automatic operation.