electronics (value IN FRONT OF the brackets)
compared to the original value of the sensitivity
when the smoke alarm device was manufactu-
red and programmed (value IN the brackets).
When the change in the smoke chamber value
is greater than 10 digits (figures) and
amination alarm was measured by the smoke
alarm device, it is strongly recommended to
replace the smoke alarm device.
If the RWM MC displays the message „ver-
schmutzt" (contaminated), but the smoke alarm
device has not yet issued contamination alarm,
the user can decide on his own whether to le-
ave the smoke alarm device installed until the
next annual maintenance or if he will replace the
smoke alarm device as a precautionary measure.
Examples:
070(075) OK
085(090) OK
075(090) not OK / (incipient) contamination
5.5 Events
The following smoke alarm device inci-
dents are considered as events:
EN
Operating Manual: RWM MC - Diagnostic device for smoke alarm devices
EN
Verschmutzungsalarm
•
(Contamination alarm)
Batteriealarm (Battery alarm)
•
Rauchalarm (Smoke alarm)
•
Temperaturalarm
•
a cont-
(Temperature alarm)
Modulalarm (eingeschränkt)
•
(Module alarm (limited))
Testkey Event (Test key event)
•
Verschmutzungsalarm
(Contamination alarm)
A contamination alar m (display as
" Ve r s . - A l a r m e " ) i s r e c o r d e d a n d
emitted by a smoke alarm device (see op-
erating manual for the smoke alarm device).
Contamination alarms occur when the cham-
ber value must be adjusted by several digits
(figures) using the integrated electronics.
39