The following table presents malfunctions that might occur during humidifier ope­
ration, explains their causes and suggests appropriate remedial action.
Cause
No water in the reservoir.
Suction piece clogged.
Excessive heat has triggered the
thermal circuit breaker of the motor.
Motor defective.
Unit has been switched off by exter­
nal humidistat
Water level in the reservoir exceeds
the maximum level mark.
Unit heavily soiled.
Whirl disk mounted incorrectly.
Suction piece has come loose.
Please contact your Condair representative in case you cannot eliminate a
particular source of trouble by yourself.
Remedy
Top up (see chapter 5).
Clean suction piece (see chapter 6).
Let the motor cool down (approxi­
mately 30 minutes), then the unit will
restart automatically.
Contact your local Condair repre­
sentative.
Check external humidistat and read­
just, as required.
Check water level.
Clean the unit (see chapter 6).
Mount whirl disk correctly.
Fix suction piece.