Location and installation

.1

Notes on correct positioning

.2
Installation work (Condair 0 S only)
1
Please observe the following notes for correct location of the Condair 505:
– Caution! The Condair 505 must not be used in hazardous locations and
areas that are exposed to water splashes.
– Locate the Condair 505 in a way that the aerosol fog spreads freely. Any
obstacle hampering the spread of the aerosol fog causes turbulence and
accumulation that may lead to condensation.
Please observe the following minimum clearance between the humidifier
and nearby objects:
– min. clearance above the unit:
– min. clearance around the unit:
– min. clearance from cold outer walls and windows:
– When using tap water or partially demineralized water the soluble mineral
salts may precipitate. Use fully demineralized water if non­precipitating
operation is required.
Consult the following information for connecting the Condair 505 S to the
water supply and the sewage line.
min. 5°
2
Water supply (1)
Supply line Ø
:
min
Admissible water pressure:
Admissible water temperature:
Water quality:
Overflow (2)
Overflow line Ø
:
min
Min. fall:
Note: It is mandatory to connect the overflow device to the sewage line.
1.0 m
0.0 m
1.00 m
1
4/6 mm (copper tube)
0,3...4,0 bar
1...40 °C
tap water, partly or fully demineralized
water
G 1/2"