Programming

4.4.5 Powerup Display.

at powerup may be changed to one of five different
displays, Unit Tag, Auto jog, Point, Alarms, or Junc-
tion Temperature. Refer to Figure 4-6 to see the
different powerup displays shown graphically. These
different types of displays are as follows:
A. Unit Tag -
The unit tag is the default display
that shows in the Command Display window. The
unit tag can be any number or alpha character string
of up to 20 characters. When selected, you will be
provided with an alphanumeric keypad. Enter the
prompt you wish to display, using the Left (←) or
Right (→) Arrow keys to move the cursor to the edit
position. PAGE selects the next page of characters,
SPC enters a Space. Press ENTER when com-
pleted, or EXIT to quit at any time without changing
the current setting.
1. Press the Menu Button on the Display Button
Bar. The Command Button Bar will display.
2. Press the PROGram Button on the Command
Button Bar. The Program Menu Box will display.
3. Use the Up (↑) or Down (↓) Arrow Keys, on the
Button Bar, to scroll to "Displays" and press the
ENTER Button. The Displays Menu Box will ap-
pear.
4. Use the Up (↑) or Down (↓) Arrow Keys, on the
Button Bar, to scroll to "Powerup disp" and press
the ENTER Button.
5. Use the Up (↑) or Down (↓) Arrow Keys, on the
Button Bar, to scroll to "Unit tag" and press the
ENTER Button and a pop-up dialog box will ap-
pear.
6. If the Unit Tag, in the pop-up dialog box, is cor-
rect, press ENTER to return to the "Unit tag" menu
item.
7. To change the Unit Tag, use the keypad to se-
lect the character and the Left (←) or Right (→)
Arrow Keys to move to a position to enter the de-
sired Unit Tag (20 characters maximum).
8. When the desired Unit Tag is displayed, press
the ENTER Key to accept the programmed Unit
Prompt and the display will return to the "Unit tag"
menu item. Press EXIT four times to return to the
initial screen display.
4-10
The unit display
B. Autojog -
The Autojog Power Up display jogs
each programmed point, with the point status and
value, at the programmed display rate which can be
1 to 60 second intervals, programmed in the Display
Program Menu - "Display rate". To program the
powerup display to Autojog, follow the instructions
below and refer to Figure 4-6.
1. Press the Menu Button on the Display Button
Bar. The Command Button Bar will display.
2. Press the PROGram Button on the Command
Button Bar. The Program Menu Box will display.
3. Use the Up (↑) or Down (↓) Arrow Keys, on the
Button Bar, to scroll to "Displays" and press the
ENTER Button. The Displays Menu Box will dis-
play.
4. Use the Up (↑) or Down (↓) Arrow Keys to scroll
to "Auto jog" and press the ENTER Button. The
screen will not change but Auto Jog is now the
Power Up Display. Press the EXIT button until you
have returned to the initial display screen.
C. Point -
The Point Power Up display allows a
programmed point to be displayed as the default
Status Window value. The point number pro-
grammed, the current value of that point, and the
engineering units will be displayed. If the point is in
alarm, the value of the point in the display will flash.
Follow the instructions below and refer to Fig. 4-6:
1. Press the Menu Button on the Display Button
Bar. The Command Button Bar will display.
2. Press the PROGram Button on the Command
Button Bar. The Program Menu Box will display.
3. Use the Up (↑) or Down (↓) Arrow Keys, on the
Button Bar, to scroll to "Displays" and press the
ENTER Button. The Displays Menu Box will ap-
pear.
4. Use the Up (↑) or Down (↓) Arrow Keys to scroll
to "Point" and press the ENTER Button.
5. If the point number is correct, press ENTER to
accept and return to the "Point" menu item.
6. To change the Unit Powerup display, use the
pop-up dialog box buttons to select the desired
point number or letter (1 - 9 or A - C) and press
ENTER. The screen will return to the "Point" menu
item.
7. Press EXIT as needed to return to the display
screen and button bar.