Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data - Camille Bauer KINAX SR 719 Betriebsanleitung

Messumformer für stellung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

KINAX SR 719
Programmable Transmitter for Position Feedback
The incorporated KINAX 2W2 consists of 2 main parts: the diffe-
rential screen capacitor D and the electronic circuitry E (Fig. 5).
D
α
R
Fig. 5. Block diagram.
The angular defl ection α of the axle is transferred to the rotor R
of the differential screen capacitor with the aid of a mechanical
coupling. It is then converted into a change of capacitance pro-
portional to the angle.
All changes to the position of the rotor result in a change in the
capacitance at the input to the microprocessor. This is transformed
into a DC current signal proportional to the measured value.
Fig. 6. Print screen example of the menu-controlled programming
software.

Technical data

Measuring input
Measured quantity:
Measuring range limits:
Measuring output
Power supply:
Output variable I
:
A
Zero point correction:
Span adjustment:
Current limitation:
Standard ranges:
2
E
μP
RS 232
Movement, stroke
0 ... 10 to 0 ... 140 mm
H = 12 to 33 V DC
Protected against wrong polarity
Load-independent DC current, pro-
portional to the input angle
Approx. ± 5%
Approx. ± 5%
I
max. 40 mA
A
4...20 mA, 2-wire connection
Data Sheet SR 719 Le – 02.08
Programming
A PC, the programming cable PK 610 plus ancillary cable and the
confi guration software 2W2 are required to program the transmitter.
(Details of the programming cable and the software are to be found
in the separate data sheet: PK 610 Le.)
The connections between
"PC ↔ PK 610 ↔ KINAX SR 719" can seen from Fig. 7. The
transmitter can be programmed either with or without the power
supply connected.
The software 2W2 is supplied on one CD and runs under
Windows 95 or higher.
The programming cable PK 610 adjusts the signal level between
the PC and the transmitter KINAX SR 719.
Programming
connector
KINAX SR719
Fig. 7. Example of the set-up for programming a KINAX SR 719 without
the power supply. For this case the switch on the interface must be set
to «ON».
External resistance (load):
Ancillary cable
Interface
PK 610
OFF
ON
OFF: Power supply by
measuring output (see
section "Electrical
connections")
ON: Power supply
provided by PC
H [V] – 12 V
R
max. [kΩ] =
ext
I
[mA]
A
H = DC power supply
I
= End value of output variable
A
Load max. [Ω] with
output 20 mA
900
600
0
10
12
24
30
Power supply [V]
Camille Bauer
36

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis