2. Scope of delivery

1 Postion Feedback Transmitter KINAX SR709
1 Operating instructions in German and English
1 Type examination certifi cate, only with ATEX-approval
3. Application
The position feedback transmitter consists of a KINAX angle
transmitter and a reduction gear which converts a linear mo-
vement into an angle of rotation of 0 ... 90°. Both parts are
contained in a robust cast aluminium housing. The mounting
part to the control valve is based on NAMUR recommendations,
(standards working group for measuring and process control in
the chemical industry).
The pick-up of the stroke movement is made by means of a slotted
lever. The adaption to strokes between 10 and 140 mm is made
with an external lever transmission and by an internal gear ratio.
The external lever transmission can be adjusted in such a way, that
the internal cam shaft makes an angle of rotation of approx. 90° for
a full stroke. The measuring range of the built-in angle transmitter
KINAX 3W2 then corresponds with this angular rotation of 90°.
Fig. 2. Operating lever set for minimum operating angle.
Fig. 3. Operating lever set for maximum operating angle.
4. Main features
• Movement- and stroke measurement with range limits 0...10 to
0...40mm
• Setting of the measuring range is achieved via adjusting the lever
system pivot point. More precise calibration is via zero and span
potentiometers / Optimum adjustment of zero and span can be
made to meet individual requirements
• Measuring output: DC current signal (load-independent, 2, 3 or
4-wire connection)
• Capacitive scanning system / Non-wearing
• Unit in fi eld type housing in cast aluminium with NAMUR mounting
part for fi tting to control valve
• With explosion prevention „Ex ia IIC T6 Gb", according to ATEX
and IECEx available

5. Technical data

5.1 Measuring input
Measured variable:
Measuring range limits:
12
Movement, stroke
0 ... 10 to 0 ... 140 mm
Operating Instructions SR709 Be – 03.13
5.2 Power supply H
DC und AC voltage:
Table 1:
Nominal voltages U
N
24 ... 60 V DC/AC
85 ... 230 V DC/AC
Power consumption:
Power supply effect
on accuracy:
1
DC voltage only
:
Max. residual ripple:
Max. current consumption: Approx. 5 mA + IA
Power supply effect
on accuracy:
Protection intrinsic safety Ex ia IIC only for connection to
certifi ed intrinsically safe circuit with the following maximum
values:
max. input voltage U i :
max. input current I i :
max. input power P i :
max. internal capacitance C i : 10nF
max. internal inductance L i :
1
Polarity reversal protection. The voltage must not fall below 12 V.
5.3 Measuring output
Output variable I
:
A
Zero point correction:
Span adjustment:
Current limitation:
Standard ranges:
Nominal voltages and tolerances
see "Table 1"
Tolerances
DC – 15 ... + 33%
AC ± 15%
only possible with
standard version, non-Ex,
with electric isolation,
with AC/DC power pack
(DC and 45 ... 400 Hz)
< 0.9 W resp. < 1.8 VA
≤ 0.1% within the admissible power
supply tolerance
12 ... 33 V
(possible with standard version, non-
Ex, without electric isolation)
12 ... 30 V
(necessary with Ex version, type of
protection "Intrinsic safety"
Ex ia IIC T6 Gb, without electric
isolation)
10% p.p.
< 0.2% within the admissible power
supply tolerance
30V
160mA
1W
is negligible
Load-independent DC current, pro-
portional to the input angle
Approx. ± 5%
Approx. + 5 / –30%
I
max. 40 mA
A
0...1 mA,
3 or 4-wire connection
0...5 mA,
3 or 4-wire connection
0...10 mA,
3 or 4-wire connection
4...20 mA, 2-wire connection or
0...20 mA, 3 or 4-wire connection
(adjustable with potentiometer)
4...20 mA,
3 or 4-wire connection
0...20 mA, 4-wire connection