Technical information

2

Regulations governing installation

2.1.
Statutory regulations governing installation
Type approvals according to ECE-R 10 (EMC) and ECE-R 122 (heaters) exist
for heaters Air Top Evo 40 / Air Top Evo 55.
For approval numbers, see Chapter 13, "Technical Data".
For installation, see Part I and Annex 7 of directive ECE-R 122 first and
foremost.
NOTE:
The provisions of these Directives are binding within the
territory governed by EU Directive 70/156/EEC and/or EC/
2007/46 (binding for new vehicle types as of 29/04/2009) and
should also be observed in countries in which there are no
special regulations!
NOTE:
Failure to follow the installation instructions will lead to the
invalidation of the type approval for the heater and
consequently the general operating permit for the vehicle.
NOTE:
Country-specific registration regulations must be complied
with.
50
Air Top Evo 40 / Air Top Evo 55
2.2.
Application of combustion heaters in vehicles for transporting
dangerous goods (ADR)
Vehicles intended for transporting dangerous goods are type-tested in
accordance with ECE-R105. The following measures have been derived for
our combustion heaters:
The electrical wiring harness must be sufficiently dimensioned to prevent
overheating. The electrical wiring harness must be sufficiently insulated.
All power circuits must be protected with fuses or automatic circuit-
breakers.
The cables must be securely fastened and routed so that the lines are
sufficiently protected against mechanical and thermal loading.
The combustion heaters must be type-tested in accordance with ECE-
R122 and must comply with Annex 9 – Additional regulations for vehicles
for transporting dangerous goods.
The combustion heaters and their exhaust gas routing shall be designed,
located, protected or covered so as to prevent any unacceptable risk of
heating or ignition of the load.
In the event of any leakage of the fuel line, the fuel shall drain to the
ground without coming into contact with hot parts of the vehicle or the
load.
The exhaust system as well as the exhaust pipes shall be so directed or
protected to avoid any danger to the load through heating or ignition.
Parts of the exhaust system situated directly below the fuel tank shall have
a clearance of at least 100 mm or be protected by a thermal shield.
The combustion heater shall be switched on manually. Programming
devices shall be prohibited. The combustion heater may be switched on
again manually after the vehicle engine has been switched off.