Installation
4
Information regarding UL
Three Phase 380 V – 500 V Voltage Range
Model
®
MOVIDRIVE
MODEL,
1100 (Size 6)
®
MOVIDRIVE
MODEL,
1320 (Size6)
®
MOVIDRIVE
MODEL,
1600 (Size 7)
®
MOVIDRIVE
MODEL,
2000 (Size 7)
®
MOVIDRIVE
MODEL,
2500 (Size 7)
1) Drives employing Type E Combination Motor Controller model MS132-12, -16, -20, -25, -32 must be installed with Current Limiter
Series S803W-SCLxxx-SR manufactured by ABB, otherwise SCCR rated 30kA/ 480 Vrms.
AC 230 V devices
Three Phase 200 V – 240 V Voltage Range
Model
®
MOVIDRIVE
MODEL,
0015 (Size 1)
®
MOVIDRIVE
MODEL,
0022 (Size 1)
®
MOVIDRIVE
MODEL,
0037 (Size 1)
®
MOVIDRIVE
MODEL,
0055 (Size 2)
®
MOVIDRIVE
MODEL,
0075 (Size 2)
®
MOVIDRIVE
MODEL,
0110 (Size 3)
®
MOVIDRIVE
MODEL,
0150 (Size 3)
®
MOVIDRIVE
MODEL,
0220 (Size 4)
®
MOVIDRIVE
MODEL,
0300 (Size 4)
1) Drives employing Type E Combination Motor Controller model MS132-12, -16, -20, -25, -32 must be installed with Current Limiter
Series S803W-SCLxxx-SR manufactured by ABB, otherwise SCCR rated 30kA/ 480 Vrms.
4.4.4

Motor overload protection

82
Betriebsanleitung – MOVIDRIVE
SCCR: 200 kA/ 500 V
SCCR: 200 kA/ 500 V
when protected by:
when protected by
Non Semiconductor Fu-
Inverse-Time Circuit
ses (currents are maxi-
Breaker (currents are
mum values)
maximum values)
300 A / 600 V
300 A / 500 V
400 A / 600 V
300 A / 500 V
400 A / 600 V
600 A / 500 V
500 A / 600 V
600 A / 500 V
600 A / 600 V
600 A / 500 V
SCCR: 200 kA/ 240 V
SCCR: 200 kA/ 240 V
when protected by:
when protected by:
Non Semiconductor Fu-
Inverse-Time Circuit
ses (currents are maxi-
Breaker (currents are
mum values)
maximum values)
30 A / 250 V
25 A / 240 V
30 A / 250 V
25 A / 240 V
30 A / 250 V
25 A / 240 V
60 A / 250 V
40 A / 240 V
60 A / 250 V
40 A / 240 V
175 A / 250 V
90 A / 240 V
175 A / 250 V
90 A / 240 V
350 A / 250 V
175 A / 240 V
350 A / 250 V
175 A / 240 V
The units are provided with load and speed-sensitive overload protection and thermal
memory retention upon shutdown or power loss.
The trip current is adjusted to 150 % of the rated motor current.
®
MDX60B/61B
SCCR: 65 kA/ 480 V:
SCCR: 65 kA/ 460 V
1)
when protected by
:
when protected by:
Type E Combination Motor Controller
-
-
-
-
-
-
-
-
-
-
SCCR: 65 kA/ 240 V
SCCR: 65 kA/ 240 V
1)
when protected by:
when protected by:
Type E Combination Motor Controller
ABB, Model MS132-10
Rockwell Automation Mo-
Rated 480 V, 5 HP
del 140M-C2E-C10, Rated
460 V, 7.5 HP
ABB, Model MS132-10
Rockwell Automation Mo-
Rated 480 V, 5 HP
del 140M-C2E-C10, Rated
460 V, 7.5 HP
ABB, Model MS132-20
Rockwell Automation Mo-
Rated 480 V, 10 HP
del 140M-D8E-C20, Rated
460 V, 15 HP
ABB, Model MS132-25
Rockwell Automation Mo-
Rated 480 V, 15 HP
del 140M-F8E-C25, Rated
460 V, 20 HP
ABB, Model MS450-40E
Rockwell Automation Mo-
Rated 480 V, 30 HP
del 140M-F8E-C45, Rated
460 V, 30 HP
ABB, Model MS450-50E
-
Rated 480 V, 40 HP
ABB, Model MS495-63E
-
Rated 480 V, 50 HP
ABB, Model MS495-90E
-
Rated 480 V, 75 HP
-
-