Bit 0: Host/Local (R/W)
0 = Local
1 = Host
Bit 1: Run/Stop (R/W)
0 = Stop
1 = Run
Bit 2: Load/Unload (R/W)
Mode (R) (på/av ledningsläge (R))
0 = Unload
1 = Load
Bit 3: Modulating (R)
0 = Not Modulating
1 = Modulating
Bit 4: Unused
Bit 5: Stopped in Auto Restart (R)
0 = Not Stopped in Auto Restart (0 = ej stoppad i automatisk omstart)
1 = Stopped in Auto Restart (1 = stoppad i automatisk omstart)
SV-62
Figur 129 : Manhattanstyrenhet Med Fixerad Hastighet Registrera 01-Status/Kontroll
Figur 130 : Manhattan Fixed Speed Controller Register Codes
Register 100: Starter Type
1 = Star-Delta
2 = Remote Starter
3 = Soft Starter
Registers 132, 135: Day
0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday
Bit 6: (värd/lokal (R/W) bit 6:) Alarm R (alarm (R))
0 = No Alarms (0 = lokal 0 = inga alarm)
1 = Alarms (1 = värd 1 = alarm)
Bit 7: (drift/stopp (R/W) bit 7:) Warning (R) (varning
(R))
0 = No Warnings (0 = stopp 0 = inga varningar)
1 = Warnings (1 = drift 1 = varningar)
Bit 8: (belastning/avlastning (R/W) bit 8:) On/Off Line
0 = Not in On/Off Line Mode (0 = avlastning 0 = Inte i
på/av ledningsläge)
1 = On/Off Line Mode (1 = belastning = på/av
ledningsläge)
Bit 9: (modulering (R) bit 9:) Mod/ACS or Mod Only
(R) (modulering/ACS eller endast modulering (R)
0 = Not in Mod/ASC Mode (0 = ej modulering 0 =inte i
modulering-/ASC-läge)
1 = Mod/ASC Mode (1 = modulering 1 = modulering-
/ASC-läge)
Bits 10-12: (oanvänd bitar 10-12:) Unused (oanvänd)
Bits 13-15: (stoppad i automatisk omstart (R) bitar
13-15:) Unit Type (R): (enhetstyp (R):) Unused
(oanvänd)
Register 114: Mode of Operation
0 = On/Off Line
1 = MOD/ACS
2 = Modulation Only
4 = Thursday
7 = Daily
5 = Friday
8 = Weekdays
6 = Saturday
9 = Weekends