Herunterladen Diese Seite drucken

Hitachi RAS-25QH1 Technische Information Seite 117

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

FORCED COOLING
¢ Units can be operated in a cooling cycle to collect refrigerant.
The conditions for execution and operation status are as follows:
[Conditions for execution]
* Forced cooling operation will be executed when the forced cooling switch is turned ON and there is no
record that all indoor units 1-4 have been operated. This system commands the main and sub
microcomputers to simultaneously execute forced cooling.
¢ The main microcomputer monitors operation records of all indoor units 1-4.
The main microcomputer always monitors the operation status of indoor units. When it detects an
operated unit, it inhibits forced cooling.
* Since the forced cooling switch is provided on the main microcomputer side, the main microcomputer
transfers the forced cooling command to the sub microcomputer via communication line between
outdoor microcomputers. When the sub microcomputer receives this request, it executes forced cooling.
[Operation status]
* Outdoor fan: Fixed at B (Lo).
© Compressor rotation speed: Fixed at 3900 min".
© Expansion valves, Reversing vaive, 15/20A switching: Same as usual operation.
[Special remarks]
¢ Thermostat turns OFF when outdoor failure occurs during forced cooling, but this is not counted.
¢ If it cannot be detected that indoor units for sub microcomputer are being operated because of a delay in
communications and the indoor unit for main microcomputer starts forced cooling, the sub
microcomputer will continue operation and the main microcomputer will release forced cooling
immediately.
¢ Since the compressor rotation speed is fixed at 3900 rpm during forced cooling, the steady speed control
when the compressor starts wil not be executed.
- 124 -

Werbung

loading

Diese Anleitung auch für:

Ras-32qh1Ram-80qh1Ras-40qh1