Error message display
Power-up Out of Range
Resolution Error
Service mode active
WTX110
Possible causes
Over/under power-up
zero setting range.
This message appears
immediately after power-
up if the scale is loaded
with a weight greater
than the set power-up
zero range (+2 %, +10
%) or less than the set
power-up zero range
(*2 %, –10 %).
Internal resolution too
low, must be at least
10 times the set
resolution
Device is set as 'Remote
Terminal,' Service mode
is active in the control
terminal
A4774-1.0 HBM: public
Interference
Remedy
Unload scale or load
scale as appropriate
Set larger digit
Use a load cell with a
lower maximum capacity
Terminate Service mode
in the control terminal